Go

Type SNG level unit

Level unit

Features
  • processor controlled level- switching device
  • up to 4 level probes + mass probe
    • single level
    • level regulation
    • open-circuit recognition
    • parameter change-over
  • Pc configurable (optional) inclusive of process monitoring + documentation
Technical specifications
  • Series: 22.5 mm rail housing
  • operating voltage: 24 VDC
  • protection class IP 20
  • operating temperature: -10 up to +50ºC
  • storage temperature -20 up to +70ºC
  • inlets: 2 or 4 independent for electrodes respectively level 1 (mass electrode respectively container)
  • sensitivity: 2 areas 0.2 KΩ…9.9 KΩ/999 KΩ; freely selectable for electrode
  • outlets: 2x relay outlet (3A/230 V) (NO; via software on NC) 2 x electronic outlet 22…24 V DC; 35 mA; PNP invertible short circuit resistant
  • time lag: turn-on / switch-off delay 0.0 to 99.9s, freely selectable for each output
Markus Wietkamp
Your contact person
Markus Wietkamp
Typical applications
  • empty and full notification in containers
  • substance monitoring in pipelines for pump protection
  • container filling / drainage with level control